Honeywell Experion C300 User Manual page 260

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

Communication and system time startup fault scenarios
Redundant Primary C300 Controller with no Memory Retention
Controller Faceplate
LEDs
Display
COMM
CB icon
Red
Status
Blinking
Red ->
LED
Blinking
Green
FTE
Blinking
Green
LEDs
Display
TS for 3
min. then
-> NODB
CB icon
Grey
Status
Blinking
Red ->
LED
Blinking
Green
FTE
Blinking
Green
LEDs
Display
TS for 1
min.
then ->
NODB
CB icon
Red
Status
Blinking
Green
LED
FTE
Blinking
Green
LEDs
Display
NODB
CB icon
Grey
244
Problem
startup.
Communication on FTE
network
• No Communication via
CDA
• Unable to establish
connection to system time
source
Communication on FTE
network
• Communication via CDA
• Unable to establish
connection to system time
source
Communication on FTE
network
• No communication via CDA
• Established connection to
system time source
Experion C300 Controller User's Guide
Honeywell
C300 Block
Station Alarm
Time Source
communication is
established:
• C300 Not
Synchronized
• Battery
Undervoltage
Internal
CDA comm Lost
Connection
WhenFTE and
CDA
communication is
established:
• C300 Not
Synchronized
• Battery
Undervoltage
CDA
C300 Not
Synchronized
SNTP
CDA comm Lost
Connection
C300 Not
Synchronized
Resolve
Note 2
Note 3
NOTE 4
R301.1
11/06