IOLINK block soft failures

Device Index value is zero upon power up
Soft Fail Message
Debug Flag Enabled
Hardware Minimum
Revision
IOLINK block soft failures
Notifications which are generated by the controller identify Soft Failure conditions in the
IOLINK interface, when indicator is lit.
Soft Fail Message
Duplicate IOL Address
232
Condition when indicator is lit
Indicates that engineering debug
firmware is running in the controller.
Non-standard behavior and/or
performance may occur.
Indicates that the controller hardware
is useable (POST passes) but it must
be upgraded for proper operation.

Table 17 IOLINK Block Soft Failures

Condition when indicator is lit
Indicates a duplicate IOLink address
has been detected.
Experion C300 Controller User's Guide
Honeywell
Corrective Action
block soft failures
for description
and corrective actions.
If not running a special image
under the direction of Honeywell
SSC, re-load the controller with the
C300 Controller firmware for the
Experion system release that is
currently running on the system.
Replace controller module.
Corrective Action
Check the secondary IOLINK
and/or IO Modules for proper
physical address.
In the C300 this is derived from the
Module's device Index, one partner
having an odd index and the other
having an even index.
R301.1
11/06