To load a CEEC300 block
Step
2
Click Tools->Load. Or, click the
load button in the toolbar.
3
With load check box checked, click the
OK button.
TIP
You can also check load progress through the four-character display on the faceplate
of the C300 Controller module. The display changes from NODB to NOEE to IDLE
upon a successful Load.
If errors are detected, they will be displayed in the Load progress dialog and you will
be asked if you want to continue the load or cancel, depending on the nature of the
error. We suggest that you cancel the load and identify and fix the errors. The
following illustration shows how error messages are typically displayed. Each message
152
Action
Experion C300 Controller User's Guide
Honeywell
Result
Calls up Load Dialog box
Initiates the load to the CEEC300 and
calls up the load progress dialog.
R301.1
11/06