Redundancy history

Become Primary command – BECMPRICMD
Secondary controller failure
Removing the powered Secondary controller module from its IOTA.
Inserting any controller module into a powered Secondary IOTA.
Single FTE link to Primary controller is lost.
Single IOL channel connected to Primary C300 I/O Link is lost.
Data communication failures with Secondary controller during synchronization.
Become Primary command – BECMPRICMD
The Become Primary command is used to cause an unsynchronized secondary module to
transition into the primary role in the absence of a partner module. Specifically, this
command applies only if the unsynchronized secondary has no view to a partner module
across the redundancy cable and the primary IP address is not occupied.
Redundancy history
The C300 and Series C FIM support a table with 16 entries of redundancy history. There
are 3 columns representing redundancy history time, state, and reason. The controller
internally implements a circular list so that only the most recent 16 entries are retained
once the number of redundancy history exceeds 16.
RDNHISTTIME – Redundancy History Time. The system time captured at the time
the entry was added to the table.
RDNHISTSTATE – Redundancy History State. Indicates milestones with respect to
redundancy-related activities like redundancy role states, compatibility states,
synchronization states, user commands, sync abort indication, and role change
indication. Set to dashes "– – –" when entry not yet initialized.
RDNHISTREASON – Redundancy History Reason. Optionally indicates rationale
for the occurrence of the associated RDNHISTSTATE entries. Includes reason for
loss-of-sync, redundancy role change, commencing initial sync, and partner
incompatibility. Set to dashes "– – –" when entry not applicable (or entry not yet
initialized).

C300 Redundancy-related notifications

This section provides listings of redundancy-related notifications implemented for the
C300 Controller. Table 14 lists notifications along with their descriptions that may occur
during controller synchronization and switchover operations.