CF9 Control Firewall

9-Port Control Firewall (CF9)

Step
digit and the rightmost switch (1) sets the ones digit.
The Device Index of the secondary controller must be set to the primary
controller's Device Index plus 1. For example, if the primary controller's
Device Index is 3 (all primary controller Device Indexes are set to an odd
number address), then set the Device Index of the secondary controller to 4.
Note: The FTE Number setting on the switches should match the
Index
12
Insert the C300 Controller module onto IOTA board making sure that the
controller circuit board mates properly with the IOTA board connector.
Secure the controller module to the IOTA board with two screws located at
each side of the plastic cover.
13
Load firmware that is identical to the firmware version currently running on
the primary controller (if not loaded already).
14
In Control Builder, select the Controller is Redundant check box of the
primary controller's configuration form.
15
Load the Secondary C300 FB and initiate an Enable Synchronization
command.
Result: The new secondary should synchronize with primary controller and
display the sync status.
CF9 Control Firewall
9-Port Control Firewall (CF9)
In the control cabinet, Control Firewall assemblies (CF9) provide connection of control
hardware (C300 Controllers, Series C FIMs, and FTEB modules) to the FTE network.
STP CAT5 cables connect the FTE-capable control hardware to the Control Firewall
30
number shown on the Controller block's configuration form Main tab.