Registering data when the remote head module is used
This section describes how to register the parameter settings of the wave data and the wave output function created with
"Create Wave Output Data" of the engineering tool to the D/A converter module.
■Registering procedure
1.
Use "Create Wave Output Data" of the engineering tool to write the parameter settings of the wave data and the wave
output function to the file register (ZR) of the CPU module of the master station.
2.
Use the JP.REMTOD instruction to transfer the parameter settings from the file register (ZR) to the D/A converter module
mounted together with the remote head module.
In this case, register the parameter settings of the wave data and the wave output function first, and then change the setting of
'CH1 D/A conversion enable/disable setting' (Un\G500).
3.
Perform operations such as requesting the start or stop of the wave output with a program.
■Program
The following describes a program that transfers the parameter settings from the file register (ZR) to the D/A converter
module mounted together with the remote head module using the JP.REMTOD instruction. The program in this section is for
the case when ZR0 is set as the start device and the parameter settings are written using "Create Wave Output Data". The file
register (ZR) to which the parameter settings are written varies depending on the specified start device. For the file register
(ZR) to which the settings are written, refer to the following.
 MELSEC iQ-R Analog-Digital Converter Module/Digital-Analog Converter Module Function Block Reference
• System configuration
(1)
(1) Master station (Network number 1, station number 0)
• Power supply module: R61P
• CPU module: R04CPU
• Master/local module: RJ71GF11-T2 (Start I/O number: 0000H to 001FH)
• Input module: RX10 (Start I/O number: 0020H to 002FH)
(2) Intelligent device station (Network number 1, station number 1)
• Power supply module: R61P
• Remote head module: RJ72GF15-T2
• D/A converter module: R60DA4 (Start I/O number: 0000H to 000FH
*1 In the RX/RY setting of the master station, set 1000H to 100FH as the start I/O number of the D/A converter module.
1 FUNCTIONS
58
1.14 Wave Output Function
(2)
*1
)