Mitsubishi Electric MELSEC iQ-R Series User Manual page 118

Melsec iq-r digital-analog converter modul
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Operating condition setting completed flag
■Device number
The following shows the device number of this input signal.
Signal name
Operating condition setting completed flag
When changing the settings, use Operating condition setting completed flag (X9) as an interlock condition to turn on and off
'Operating condition setting request' (Y9).
For the buffer memory addresses which require turning on and off of 'Operating condition setting request' (Y9) to enable the
changed values, refer to the following.
Page 124 List of buffer memory addresses
In the following state, 'Operating condition setting completed flag' (X9) turns off.
• When 'Operating condition setting request' (Y9) is on
Module READY (X0)
Operating condition setting
completed flag (X9)
Operating condition
setting request (Y9)
APPENDICES
116
Appendix 2 I/O Signals
CH1
CH2
X9
Controlled by the D/A converter module
Controlled by the program
ON
ON
CH3
CH4
CH5
ON
OFF
ON
CH6
CH7
CH8