Mitsubishi Electric MELSEC iQ-R Series User Manual page 23

Melsec iq-r digital-analog converter modul
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■In the synchronization normal output mode
Execution
CH1 D/A conversion
status
enable/disable setting
(Un\G500)
CH1 Output enable/disable
flag (Y1)
Analog output HOLD/
CLEAR setting
External
Analog output produced when the
power
CPU module is in the RUN status
supply
Analog output produced when the
READY flag
CPU module is in the STOP state
(X7): On
Analog output produced when the
CPU module is in the stop error
state
External power supply READY flag (X7): Off
Analog output produced when a watchdog timer
*1
error
occurs
*1 The error occurs due to a hardware failure of the D/A converter module or other causes. 'Module READY' (X0) and the RUN LED of the
D/A converter module turn off.
When a watchdog timer error occurs, 'Module READY' (X0) and the RUN LED of the D/A converter module turn off.
Setting procedure
Set "Analog output HOLD/CLEAR setting" to "HOLD" or "CLEAR".
Navigation window  [Parameter]  [Module Information]  Module name  [Module parameter]  "Basic settig" 
"Output mode setting function"
Precautions for when the remote head module has been mounted
When the D/A converter module has been mounted on the remote head module, set whether to hold or clear the analog
output value that has been output when the host station is disconnected with "CPU error output mode setting" of the module
parameter.
The following describes the settings required for using "CPU error output mode setting".
• Enable the station-based block data assurance for cyclic data on the sending side.
• To hold the analog output value, set "CPU error output mode setting" to "Hold". The analog output HOLD/CLEAR function
setting is disabled.
This setting is enabled for each module and cannot be set for each channel. To match the output status of when a stop error
occurs or the CPU module is in the STOP state and that of when the host station is disconnected, set "Analog output HOLD/
CLEAR setting" to the same value in all the channels.
Operating status
The analog output value is held.
The analog output value is cleared.
(The offset value is output.)
*1 "CPU error output mode setting" is enabled in the following cases.
 When the host station is disconnected due to a network error
 When the data link is stopped by the CC-Link IE Field Diagnostics of the engineering tool
Enable
Enable
HOLD
CLEAR
CH1 Synchronization digital value (Un\G9500)
Hold
Offset value
Hold
Offset value
0V/0mA
0V/0mA
0V/0mA
0V/0mA
CPU error output mode setting
Hold
Clear
Disable
HOLD or CLEAR
Offset value
*2
Offset value
Offset value
0V/0mA
0V/0mA
*1
Analog output HOLD/CLEAR setting
(Set the same value in all the channels.)
HOLD
CLEAR
1.5 Analog Output HOLD/CLEAR Function
Disable
1
Enable or disable
HOLD or CLEAR
0V/0mA
0V/0mA
0V/0mA
0V/0mA
0V/0mA
1 FUNCTIONS
21