Wave pattern
To use the wave output function, select any points from the registered wave data for each channel and set the wave pattern.
The following table lists the setting contents for the wave pattern.
Setting item
Wave pattern start address setting
Wave pattern data points setting
If the address value (total of the set values for "Wave pattern start address setting" and "Wave pattern data points setting" - 1)
exceeds the last buffer memory address (Un\G89999) of the wave data registry area, an error occurs. The error code
(1D9H) is stored in 'Latest error code' (Un\G0), 'Error flag' (XF) turns on, and the ERR LED turns on.
Ex.
Setting example to output different waves from CH1 and CH2
Wave data registry area
(Un\G10000 to Un\G89999)
Wave data registry area
(Un\G10000)
Setting item
CH1 Wave pattern start address setting
CH1 Wave pattern data points setting
CH2 Wave pattern start address setting
CH2 Wave pattern data points setting
Description
Set the start address of the wave pattern to be output for each channel. The D/A conversion starts from the digital
input value of the buffer memory address set in this area and the converted values are output sequentially.
This area is for setting the points of the wave pattern to be output for each channel. From the start address of the
wave pattern, the D/A conversion starts for the points of wave data set in this area and the converted values are
output.
CH1
CH2
Wave pattern
Wave pattern
10000 points
8000 points
Empty
(62000 points)
80000 points
Setting value
10000
10000
20000
8000
Wave data registry area
(Un\G89999)
1 FUNCTIONS
1.14 Wave Output Function
1
41