CH1 Rate control enable/disable setting
Set whether to enable or disable the rate control.
For the rate control function, refer to the following.
Page 30 Rate Control Function
Setting value
0
1
If a value other than the above is set, a rate control enable/disable setting range error (error code: 1B8H) occurs.
The rate control function cannot be used when the wave output function is used. In the channel for which Enable (0) is set
while the wave output function is being used, a rate control setting error in wave output mode (alarm code: 0B3H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Rate control enable/disable setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Disable (1) for all channels.
Rate control enable/disable setting [Q compatible mode]
When the Q compatible mode function is used, set whether to enable or disable the rate control.
The following shows the setting details in the Q compatible mode.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
(2)
(1) 0: Rate control enable, 1: Rate control disable
(2) b4 to b15 of the R60DA4 and b8 to b15 of the R60DAV8 and R60DAI8 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Rate control enable/disable setting
APPENDICES
156
Appendix 3 Buffer Memory
CH1
509
b8
b7
b6
b5
b4
0
0
0
CH8
CH7
CH6
CH5
CH1
46
Description
Enable
Disable
CH2
CH3
CH4
709
909
1109
b3
b2
b1
b0
CH4
CH3
CH2
CH1
(1)
CH2
CH3
CH4
CH5
CH6
CH7
1309
1509
1709
CH5
CH6
CH7
CH8
1909
CH8