CH1 Scaling upper limit value
Set the range of the scale conversion.
For the scaling function, refer to the following.
Page 23 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling upper limit value
CH Scaling upper limit value (When the Q
compatible mode function is used)
■Setting range
The setting range is from -32000 to 32000. In the channel where a value out of the range is set, a scaling setting range error
(error code: 1A1H) occurs. In the channel where a set value does not satisfy the condition "scaling upper limit value 
scaling lower limit value", a scaling upper/lower limit value setting error (error code: 1A2H) occurs.
When 'CH1 Scaling enable/disable setting' (Un\G502) is set to Disable (1), the setting for 'CH1 Scaling upper limit value'
(Un\G504) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all channels.
CH1 Scaling lower limit value
Set the range of the scale conversion.
For the scaling function, refer to the following.
Page 23 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling lower limit value
CH Scaling lower limit value (When the Q
compatible mode function is used)
■Setting range
The setting range is from -32000 to 32000. In the channel where a value out of the range is set, a scaling setting range error
(error code: 1A1H) occurs. In the channel where a set value does not satisfy the condition "scaling upper limit value 
scaling lower limit value", a scaling upper/lower limit value setting error (error code: 1A2H) occurs.
When 'CH1 Scaling enable/disable setting' (Un\G502) is set to Disable (1), the setting for 'CH1 Scaling lower limit value'
(Un\G506) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all channels.
APPENDICES
154
Appendix 3 Buffer Memory
CH1
CH2
CH3
504
704
904
55
57
59
CH1
CH2
CH3
506
706
906
54
56
58
CH4
CH5
CH6
1104
1304
1504
61
63
65
CH4
CH5
CH6
1106
1306
1506
60
62
64
CH7
CH8
1704
1904
67
69
CH7
CH8
1706
1906
66
68

Hide quick links: