Wave data registry area
This area is for registering wave data for analog output in the wave output mode.
The setting range depends on the set output range. The setting range is shown below.
Output range
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
-10 to 10V
In the channel where the wave data with a value out of the above setting range set is output, a digital value setting range error
(error code: 191H) occurs and 'Error flag' (XF) turns on. The wave output operations continue to be performed. However,
the analog output value corresponding to a digital input value out of the setting range is fixed to the maximum or minimum
value of the output range.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Wave data registry area
Wave data registry area (When the Q compatible
mode function is used)
Setting range
-768 to 32767 (practical range: 0 to 32000)
-32768 to 32767 (practical range: -32000 to 32000)
CH1
CH2
CH3
10000 to 89999
10000 to 89999
CH4
CH5
CH6
Appendix 3 Buffer Memory