Mitsubishi Electric MELSEC iQ-R Series User Manual page 56

Melsec iq-r digital-analog converter modul
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Starting/stopping/pausing wave output
■Starting the wave output
The wave output can be started by the following procedures after the wave data registration.
1.
Turn on 'CH1 Output enable/disable flag' (Y1).
The value is output in analog according to the setting in 'CH1 Output setting during wave output stop' (Un\G524).
2.
Set Wave output start request (1) to 'CH1 Wave output start/stop request' (Un\G462).
When Wave output stop request (0) or Wave output pause request (2) is changed to Wave output start request (1), the wave
output is started.
■Stopping the wave output
To stop the wave output at any timing during the wave output, set Wave output stop request (0) to 'CH1 Wave output start/stop
request' (Un\G462). When Wave output start request (1) or Wave output pause request (2) is changed to Wave output stop
request (0), the wave output is completely stopped. When the wave output is stopped, Wave output stop (0) is stored to 'CH1
Wave output status monitor' (Un\G401). The wave output cannot be resumed at the stop point.
When outputting the wave pattern for the count set in 'CH1 Wave pattern output repetition setting' (Un\G530) is finished, the
wave output stops.
CPU module status
CH1 D/A conversion enable/disable
setting (Un\G500)
CH1 Output enable/disable
flag (Y1)
CH1 Wave output start/stop request
(Un\G462)
CH1 Wave output status monitor
(Un\G401)
Wave data
Output set in CH Output setting
during wave output stop (Un\G524)
1 FUNCTIONS
54
1.14 Wave Output Function
OFF
Wave output stop
request (0)
Wave output stop (0)
Analog output
Offset value
RUN
D/A conversion enable (0)
(2)
ON
Wave output stop
Wave output start
request (1)
request (0)
Wave output (1)
Wave output stop (0)
Wave output ends.
(1)
(1): Wave output starts when Wave output start request (1) is set to CH1
Wave output start/stop request (Un\G462).
(2): To execute wave output again, set Wave output stop request (0) to
CH1 Wave output start/stop request (Un\G462), then change the value
to Wave output start request (1).
(3): Wave output stops when Wave output stop request (0) is set to CH1
Wave output start/stop request (Un\G462) during the wave output.
Wave output
Wave output stop
start request
request (1)
(1)
Wave
Wave output stop (0)
output (1)
(3)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60dav8R60da4R60dai8

Table of Contents