In the Chassis (IP00) and NEMA 1 units it is also possible to connect the
fieldbus from the top of the unit as shown on the picture to the right. On
the NEMA 1 unit a cover plate must be removed.
Kit number for fieldbus top connection: 176F1742
3
Installation of 24 Volt external DC Supply
Torque: 0.5 - 0.6 Nm (5 in-lbs)
Screw size: M3
24 VDC external supply can be used as low-voltage supply to the control card and any option cards installed. This enables full operation of the LCP
(including parameter setting) without connection to mains. Please note that a warning of low voltage will be given when 24 VDC has been connected;
however, there will be no tripping.
Use 24 VDC supply of type PELV to ensure correct galvanic isolation (type PELV) on the control terminals of the frequency converter.
3.6.21 Access to Control Terminals
All terminals to the control cables are located beneath the LCP. They are accessed by opening the door of the IP21/ 54 version or removing the covers
of the IP00 version.

3.6.22 Electrical Installation, Control Terminals

To connect the cable to the terminal:
1.
Strip insulation by about 9-10 mm
2.
Insert a screwdriver
3.
Insert the cable in the adjacent circular hole.
4.
Remove the screwdriver. The cable is now mounted in the terminal.
To remove the cable from the terminal:
1.
Insert a screw driver
2.
Pull out the cable.
1)
Max. 0.4 x 2.5 mm
70
1)
in the square hole.
1)
in the square hole.
MG.20.P3.02 - VLT
VLT AQUA High Power Operation Instructions
Illustration 3.52: Top connection for fieldbus.
No.
Function
35 (-), 36 (+)
24 V external DC supply
®
is a registered Danfoss trademark