6 General Specifications
Mains Supply 3 x 525- 690 VAC
6
Max. input current
1) For type of fuse see section
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cable
conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss
in the frequency converter and opposite. If the switching frequency is increased compared to the default setting, the power losses may rise
significantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.
(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
182
P710
Typical Shaft output at
560
550 V [kW]
Typical Shaft output at
750
575 V [HP]
Typical Shaft output at
710
690 V [kW]
Enclosure
IP21,
54
without/ with options
F1/ F3
cabinet
Output current
Continuous
763
(at 550 V) [A]
Intermittent (60 s over-
839
load, at 550 V) [A]
Continuous
730
(at 575/ 690 V) [A]
Intermittent (60 s over-
803
load, at 575/690 V) [A]
Continuous KVA
727
(at 550 V) [KVA]
Continuous KVA
727
(at 575 V) [KVA]
Continuous KVA
872
(at 690 V) [KVA]
Continuous
743
(at 550 V ) [A]
Continuous
711
(at 575 V) [A]
Continuous
711
(at 690 V) [A]
Max. cable size,motor
[mm
2
(AWG
2)
)]
Max. cable size,mains
[mm
2
(AWG
2)
)]
Max. cable size, load-
sharing [mm
2
(AWG
2)
)]
Max. cable size, brake
[mm
2
(AWG
2)
)
Max. external pre-fuses
[A]
1)
Est. power loss
at rated max. load [W]
10771
4)
, 575 V, F1 & F2
Est. power loss
at rated max. load [W]
11315
4)
, 690 V, F1 & F2
Max added losses of
Circuit Breaker or Dis-
422
connect & Contactor,
F3 & F4
Max Panel Options Los-
ses
Weight,enclosure IP21,
1004/ 1299
IP 54 [kg]
Weight, Rectifier
102
Module [kg]
Weight, Inverter
102
Module [kg]
Efficiency
4)
Output frequency
Heatsink overtemp. trip
Power card amb. trip
Fuses.
MG.20.P3.02 - VLT
VLT AQUA High Power Operation Instructions
P800
P900
670
750
950
1050
800
900
F1/ F3
F1/ F3
889
988
978
1087
850
945
935
1040
847
941
847
941
1016
1129
866
962
828
920
828
920
8x150
(8x300 mcm)
8x240
(8x500 mcm)
4x120
(4x250 mcm)
4x185
(4x350 mcm)
1600
12272
13835
12903
14533
526
610
400
1004/ 1299
1004/ 1299
102
102
102
136
0.98
0-500 Hz
85 °C
68 °C
®
is a registered Danfoss trademark
P1M0
P1M2
850
1000
1150
1350
1000
1200
F2/ F4
F2/ F4
1108
1317
1219
1449
1060
1260
1166
1386
1056
1255
1056
1255
1267
1506
1079
1282
1032
1227
1032
1227
12x150
(12x300 mcm)
6x185
(6x350 mcm)
2000
15592
18281
16375
19207
658
855
1246/ 1541
1246/ 1541
136
136
102
102