Advertisement

5. How to Install

5.2.10. Electrical Installation, Control Terminals

To mount the cable to the terminal:
1.
2.
3.
4.
To remove the cable from the terminal:
5
1.
2.
1)
Max. 0.4 x 2.5 mm
Assembling of IP55 / NEMA TYPE 12 housing
with mains disconnector
5.2.11. Basic Wiring Example
1.
2.
Default settings:
18 = latched start
27 = stop inverse
94
Strip isolation of 9-10 mm
1)
Insert a screw driver
in the square
hole.
Insert the cable in the adjacent cir-
cular hole.
Remove the screw driver. The cable
is now mounted to the terminal.
Insert a screw driver
1)
in the square
hole.
Pull out the cable.
Mount terminals from the accessory
bag to the front of the frequency
converter.
Connect terminals 18 and 27 to +24
V (terminal 12/13)
MG.11.B2.02 - VLT
1.
2.
Illustration 5.15: Terminal 37 available with Safe
Stop Function only!
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Design Guide
3.