TROUBLESHOOTING
9.5.6 Error codes F100
QJ71PB92V)
Error Code
LED Status
F100
FAULT LED ON
H
F101
FAULT LED ON
H
F102
H
F103
H
FAULT LED ON
F104
H
F105
H
PRM SET LED
F106
H
flashing
F107
FAULT LED ON
H
F108
FAULT LED ON
H
PRM SET LED
F109
H
flashing
PRM SET LED
F10A
H
flashing
F10B
FAULT LED ON
H
PRM SET LED
F10C
H
flashing
PRM SET LED
F10D
H
flashing
F10E
FAULT LED ON
H
F10F
FAULT LED ON
H

9.5.6 Error codes F100H to FBFFH (Local diagnostic information of the QJ71PB92V)

to FBFF
H
H
Table9.9 Error codes F100
Error Description
FDL address No. of a DP-Slave is
duplicated with that of the DP-Master in the
parameter settings.
No DP-Slaves are set up for I/O data
exchange.
Hardware failure
Parameters have not been written to the
flash ROM.
The parameters or operation mode read
from the flash ROM are corrupted.
Unable to access the flash ROM.
Or failed to initialize the flash ROM.
Parameters of the QJ71PB92D were
written with the QJ71PB92D-compatible
function disabled.
Parameters of the QJ71PB92V were
written with the QJ71PB92D-compatible
function enabled.
Unable to read the operation mode
registered to the flash ROM.
In the parameter settings, there is a DP-
Slave whose I/O data size is set to 0 byte.
Parameter error
Hardware failure
Hardware failure or parameter error
9.5 Error Codes
Error codes F100
(Local diagnostic information of the
to FBFF
H
H
Check the FDL addresses of the DP-Master and
DP-Slaves, and set correct parameters without
duplication.
Check the following and correct the setting so that
one or more DP-Slaves can exchange I/O data.
• Is the slave parameter, "Slave is active"
checked?
• In the temporary slave reservation, haven't all of
DP-Slaves been specified as reserved stations?
Replace the QJ71PB92V.
If the same error occurs again, please consult your
local Mitsubishi representative.
Write the parameters.
Initialize the flash ROM, and then write the
parameters and operation mode.
If the same error occurs again, replace the
QJ71PB92V.
Initialize the flash ROM.
If the same error occurs again, replace the
QJ71PB92V.
• Change the module selected in the GX
Configurator-DP project to QJ71PB92V, and
write the parameters.
• Check Switch 2 of the intelligent function module
switches. (
• Change the module selected in the GX
Configurator-DP project to QJ71PB92D, and
write the parameters.
• Check Switch 2 of the intelligent function module
switches. (
Initialize the flash ROM.
If the same error occurs again, replace the
QJ71PB92V.
Check the slave parameters, and make the setting
again to ensure that the I/O data size of each DP-
Slave is 1 byte or more.
Initialize the flash ROM.
If the same error occurs again, please consult your
local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Enable the master parameter, "Calculate time", and
write the parameters. If the same error occurs
again, please consult your local Mitsubishi
representative.
to F10F