TROUBLESHOOTING
Error Code
E564
Application error was detected on the DP-Slave side.
H
Request-not-supported error was detected on the DP-Slave
E565
H
side.
E566
Incorrect index was detected on the DP-Slave side
H
E567
Incorrect data length was detected on the DP-Slave side.
H
E568
Incorrect slot number was detected on the DP-Slave side.
H
E569
Incorrect data type was detected on the DP-Slave side.
H
Access to an access-disabled area was attempted from the
E56A
H
DP-Slave side.
E56B
Access is not available on the DP-Slave side.
H
E56C
The access was rejected on the DP-Slave side.
H
E56D
Incorrect access range was detected on the DP-Slave side.
H
E56E
Incorrect request was detected on the DP-Slave side.
H
E56F
Incorrect data type was detected on the DP-Slave side.
H
Incorrect parameter in the request was detected on the DP-
E570
H
Slave side.
Resource error was detected during read processing on the
E571
H
DP-Slave side.
Resource error was detected during write processing on the
E572
H
DP-Slave side.
E573
The resource is already in use on the DP-Slave side.
H
E574
There is no resource that can be used on the DP-Slave side.
H
E575
Incorrect parameter exists in the ACK request.
H
E576
H
There is no alarm for which ACK can be requested.
E580
H
E581
The alarm specified for ACK request is not found.
H
E582
Use of the alarm function is not allowed.
H
E590
H
E591
H
E592
H
E593
H
E594
H
E595
Hardware failure
H
E596
H
E597
H
E598
H
E599
H
E59A
H
E59B
Acyclic communication is executed to the same DP-Slave.
H
E59C
There is no executable resource.
H
E59D
There is an invalid parameter setting.
H
9
- 22
9.5 Error Codes
9.5.4 Error codes E500H to E5FFH (Error codes generated when reading alarms)
Table9.7 Error codes E500H to E5FFH (Continued)
Error Description
Error codes E564
Action
Check if the request data supported by the DP-Slave is
correctly set or not, and retry.
For details, refer to the manual for the DP-Slave.
Check the alarm status on the specified DP-Slave and
retry.
Check if the DP-Slave supports the alarm function or not,
and retry.
Please consult your local Mitsubishi representative.
Verify that the Acyclic communication is completed, and
retry.
Check the parameter settings and then retry.
to E59D