Mitsubishi Electric Melsec Q Series User Manual page 149

Profibus-dp master module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

4
FUNCTIONS
POINT
(2) Wiring for using the QJ71PB92D-compatible function
Except for the PROFIBUS interface connector position and no terminating resistor,
the wiring is the same as the QJ71PB92D.
(a) PROFIBUS interface connector position
(b) Bus terminator
Remark
GX Configurator-DP Version 7.00A cannot be used.
For GX Configurator-DP Version 7.00A, upgrade it to Version 7.01B or later.
For version upgrades, please consult your local Mitsubishi representative.
The PROFIBUS interface connector position on the QJ71PB92V is moved up by
17mm (0.67 inch), compared with the QJ71PB92D.
If the PROFIBUS cable is not long enough, extend the cable length by using an
extension connector.
QJ71PB92D
Figure 4.32 PROFIBUS Interface Connector Position
The QJ71PB92V does not have a built-in bus terminator.
When the bus terminator setting switch on the QJ71PB92D has been set to ON,
use a connector with a built-in bus terminator for the QJ71PB92V.
For wiring specifications for the bus terminator of the QJ71PB92V, refer to Section
5.5.1.
For details on PROFIBUS cables and connectors, access the following website.
• PI: www.profibus.com
4.9 QJ71PB92D-Compatible Function
QJ71PB92V
17mm
1
2
3
4
5
6
7
8
4
- 40