Output Setting Function For Cpu Stop Error - Mitsubishi Electric FX5-DP-M User Manual

Melsec iq-f series
Table of Contents

Advertisement

4.6

Output Setting Function for CPU Stop Error

This function can be set whether to stop data exchange with DP-Slaves when a CPU stop error occurs to the CPU module
mounting the FX5-DP-M.
The output status for CPU stop errors can be configured in the following.
[Navigation window]  [Parameter]  [Module Information]  [FX5-DP-M]  [Module Parameter]  [Application
setting]
When "Clear" is selected for "CPU Error Output Mode Setting"
• Data exchange with the DP-Slave is interrupted.
• The output data of the FX5-DP-M buffer memory is cleared and is not sent.
• Input data that was already received from the DP-Slave when the CPU module stop error occurred is held in the FX5-DP-M
buffer memory.
Data output after I/O data exchange is stopped may be output from the DP-Slave to an external device
depending on the settings of the DP-Slave. (Refer to the manual for the DP-Slave)
4.6 Output Setting Function for CPU Stop Error
4
4 FUNCTIONS
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents