Mitsubishi Electric Melsec Q Series User Manual page 63

Profibus-dp master module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
(4) Local FDL address display area (Un\G2257)
The FDL address of the local station is stored.
(5) Offline test status area (Un\G2258)
The self-diagnostics test details or test result is stored in this area.
For details on the self-diagnostics test, refer to Section 5.4.
Table3.12 Local FDL Address Display Area (Un\G2257)
Stored Value
0000
to 007D
H
H
The FDL address of the local station
(0 to 125)
FFFF
Parameter not set
H
* 1 When the QJ71PB92V is mounted on a redundant system, the following address is stored.
When it is in the control system: Control master FDL address
When it is in the standby system: Standby master FDL address
3.4 Buffer Memory
3.4.2 Local station information area
Description
*1
1
2
3
4
5
6
7
8
3
- 22