Error Code
E469
Incorrect data type was detected on the DP-Slave side.
H
Access to an access-disabled area was attempted from
E46A
H
the DP-Slave side.
E46B
Access is not available on the DP-Slave side.
H
E46C
The access was rejected on the DP-Slave side.
H
Incorrect access range was detected on the DP-Slave
E46D
H
side.
E46E
Incorrect request was detected on the DP-Slave side.
H
E46F
Incorrect data type was detected on the DP-Slave side.
H
Incorrect parameter in the request was detected on the
E470
H
DP-Slave side.
Resource error was detected during read processing on
E471
H
the DP-Slave side.
Resource error was detected during write processing on
E472
H
the DP-Slave side.
E473
The resource is already in use on the DP-Slave side.
H
There is no resource that can be used on the DP-Slave
E474
H
side.
The service not available for the specified DP-Slave was
E475
H
requested.
Memories used for request processing are insufficient on
E476
H
the DP-Slave side.
E477
The DP-Slave side made this service invalid.
H
E478
The DP-Slave side did not respond to the request.
H
The FDL address of the target DP-Slave is out of the
E480
H
range.
The FDL address specified for the target DP-Slave
E481
H
belongs to the local station (QJ71PB92V).
E482
INITIATE error response
H
E483
Invalid Alignment setting
H
E484
The CommRef number is incorrect.
H
E485
Total size of S Len and D Len is out of range.
H
E490
Physical execution error detected.
H
E491
Execution error on the protocol was detected.
H
E492
Execution error on the application was detected.
H
E4A0
Read error was detected on the DP-Slave side.
H
E4A1
Write error was detected on the DP-Slave side.
H
E4A2
Module error was detected on the DP-Slave side.
H
E4A3
Processing on the DP-Slave side is not available.
H
E4A4
Application error was detected on the DP-Slave side.
H
Request-not-supported error was detected on the DP-
E4A5
H
Slave side.
E4A6
Incorrect index was detected on the DP-Slave side.
H
E4A7
Incorrect data length was detected on the DP-Slave side.
H
E4A8
Incorrect slot number was detected on the DP-Slave side.
H
E4A9
Incorrect data type was detected on the DP-Slave side.
H
9
- 18
9.5 Error Codes
9.5.3 Error codes E400H to E4FFH (Error codes generated during acyclic communication)
Table9.6 Error codes E400H to E4FFH (Continued)
Error Description
Error codes E469
Action
Check if the request data supported by the DP-Slave is
correctly set or not, and retry.
For details, refer to the manual for the DP-Slave.
Check if the specified FDL address is correct, and retry.
Check the detailed error codes 1 to 3 and take corrective
actions.
Check if the specified Alignment is correct, and retry.
Check if the specified CommRef number is correct, and
retry.
Adjust the total size of S Len and D Len to 230 bytes or
less, and retry.
Check the detailed error codes 2 and 3, and take
corrective actions.
Check if the request data supported by the DP-Slave is
correctly set or not, and retry.
For details, refer to the manual for the DP-Slave.