Mitsubishi Electric Melsec Q Series User Manual page 81

Profibus-dp master module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
POINT
Order of assignment
(1) Data are assigned to the Diagnostic information area (for mode 3) in the order
of the parameters set in GX Configurator-DP (in the order of FDL addresses).
The actual order of assignment can be checked in Address information area
(for mode 3) (Un\G22528 to Un\G22777) or in "Documentation of I/O-
Mapping" of GX Configurator-DP.
(2) When parameters have been modified (deletion or addition of DP-Slave(s))
on GX Configurator-DP, the buffer memory is reassigned.
After modifying parameters, review the sequence program.
If some DP-Slaves are expected to be connected to the network in the future,
setting them as Reserved stations in the parameter setting eliminates the
need to check the sequence program. (
(3) The information in Diagnostic information area (for mode 3) (Un\G23072 to
Un\G23321) is not cleared even if the problem occurred on the DP-Slave has
been solved.
To clear the information in Diagnostic information area (for mode 3)
(Un\G23072 to Un\G23321), turn ON the Diagnostic information area clear
request signal (Y02).
3.4 Buffer Memory
3.4.6 Diagnostic information area
Section 6.5)