Status And Diagnosis Object - Festo CPX-FB36 Instruction Manual

Bus node network protocol ethernet/ip modbus tcp industrial ethernet 2-port
Hide thumbs Also See for CPX-FB36:
Table of Contents

Advertisement

C. EtherNet/IP Objects of the CPX-FB36
C.4.3 "Status and Diagnosis Object"
Attr.
Access
Description
no.
1
Get
Status bits (8 bit)
Source of error: Bit 0: Valve
Error type:
2
Get
Number of the first module in which a fault has
occurred
3
Get
Diagnostic status
4
Get
Error number
5
Get/Set
Address I/O diagnostic interface
16 output bits (task data) of the I/O diagnostic inter­
face
6
Get
Data I/O diagnostic interface
16 input bits (reply data) of the I/O diagnostic inter­
face
Tab. C/25: Attributes of the status and diagnostics object
Festo CPX-FB36-EN en 1611a English
Object class:
133
Instances:
1
The status bits and the I/O diagnostic interface are mapped
here.
Bit 1: Output
Bit 2: Input
Bit 3: Analogue/technology module
Bit 4: Undervoltage
Bit 5: Short circuit/overload
Bit 6: Wire break
Bit 7: Other error
d
Type
BYTE
BYTE
BYTE
BYTE
WORD
WORD
Function
no.
1936
1937
1938
C-23