2. Preparing for commissioning
Festo CPX-FB36-EN en 1611a English
Bus node not configured
LED indicator
Status and significance
[MS]
– Device ready for operation
Lights up green
[PS]
– Power supply (Power System, PS) is OK
– Operating voltage present
(in the approved range)
Lights up green
[NS]
– Network communication present but not con­
figured (operating status "online"),
In this case, this is correct, because the bus
node is not configured.
Flashes green
[PL]
– Load voltage present
(in the approved range)
Lights up green
[TP1], [TP2]
– Device is correctly connected to the bus node
– Internal communication between bus node and
device 1 or device 2 is error free
– Operating and load voltage present
Lights up green
(in the approved range)
1) Display dependent on monitoring and signal from the connected
device.
Tab. 2/4:
Status LEDs after switch-on –
bus node not configured
1)