Setting Up A "Listen Only" Connection - Festo CPX-FB36 Instruction Manual

Bus node network protocol ethernet/ip modbus tcp industrial ethernet 2-port
Hide thumbs Also See for CPX-FB36:
Table of Contents

Advertisement

3. Commissioning

3.1.5 Setting up a "Listen only" connection

Festo CPX-FB36-EN en 1611a English
When the participant properties have been configured (e.g.
by installation of an EDS file), the following steps are required
for configuration.
1. Install CPX terminal and set IP addressing (è 1.3.5).
2. Make connection to the bus node.
In the "Studio 5000" software, use the "Generic Ethernet
Device" profile for this purpose (è 3.1.2).
3. Open the "Module Properties" dialogue.
4. Select the data format DATA - SINT from the "Comm
Format" list field (è Fig. 3/10).
5. Enter the following values in the "Connection Parameters"
field:
"Connection
Parameters"
"Input"
"Output"
"Configuration"
Tab. 3/6:
Properties for "Connection parameters"
6. Enter IP address of the bus node.
"Assembly
"Size"
Instance"
101
Number of inputs
set on the bus
node
1
0
102 ("Configura­
0
tion Assembly")
3-21