Ethernet Link Object - Festo CPX-FB36 Instruction Manual

Bus node network protocol ethernet/ip modbus tcp industrial ethernet 2-port
Hide thumbs Also See for CPX-FB36:
Table of Contents

Advertisement

C. EtherNet/IP Objects of the CPX-FB36
C.2.4 "Ethernet Link Object"
C-12
Object class:
246
Instances:
2
One instance per Ethernet port:
Instance 1 corresponds to Ethernet port X1
Instance 2 corresponds to Ethernet port X2
Via the Ethernet Link Object, you can undertake extended
settings for the Ethernet connection (è section 1.3.6).
Attr.
Access
Description
no.
1
Get
Interface Speed
2
Get
Interface Status Flags
3
Get
Physical MAC address
6
Get/Set
Interface Control
– Control Bits
– Forced Interface Speed
Tab. C/10: Network settings with Ethernet Link Object
Examples:
To set Port X1 permanently to 100 Mbit/s, full duplex (Auto-
Negotiation off ), the following values must be written in
Attribute 6, Instance 1: [0002
To activate Auto-Negotiation, the following values must be
written in Attribute 6, Instance 1: [0001
Further details can be found in the EtherNet/IP specification.
d
][0064
].
h
h
][0000
h
Festo CPX-FB36-EN en 1611a English
Type
UDINT
DWORD
ARRAY of
6 USINT
STRUCT of
WORD,
UINT
].
h

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents