3. Commissioning
3.1.2 Configuration with "Generic Ethernet Module"
Festo CPX-FB36-EN en 1611a English
This section describes the manual configuration of the bus
node as participant in a a controller from Allen-Bradley with
the help of the "Studio 5000" software (V 26.01.00) from
Rockwell Automation.
The fundamental aspects of this description also apply for
other control systems.
Integrate participants into the project and configure
them
Configuration of the bus node can only take place if there is
no online connection to the controller.
1. Terminate an existing online connection to the higher-or
der controller:
[Communications] , [Go Offline]
2. Open "Select Module Type" dialogue:
In the "Controller Organizer" window in the "I/O Configur
ation" directory, click on "Ethernet" with the right mouse
button and select "New Module" in the context menu
(è Fig. 3/4).
3. In the "Catalogue" tab, select the module with the de
scription "Generic Ethernet Module" from the table.
Fig. 3/9:
Integrating a bus node as a Generic Ethernet Module