Table 9. Aim Ma Connection Table - Honeywell Touchpoint Pro Technical Handbook

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

5.2.14 Connecting to an Analogue Input Module (4 – 20 mA)
The Analogue Input Module mA (AIM mA) is a sink module that accepts 4-20 mA source signals from 2-wire or 3-wire field
devices. The sensors connect via the front-face terminals.
The module can supply 18-32 VDC (24 VDC nominal) to the field devices at a maximum current of 1 A per channel, with the
additional limitation that the total current drawn from the module must not exceed 2 A at 65 °C ambient or 4 A at 55 °C
ambient.
Voltage outputs are overload protected.
The following diagrams show how to connect various types of device or sensor.
Part. No. 2400M2501_6
MODBUS INSTALLATION
Channel
Terminal
Input 1
Input 2
Input 3
Input 4

Table 9. AIM mA Connection Table

Device
Figure 49.
Label
Field Device
1
+V
24 VDC
4 – 20 mA Signal
2
SIG
–V
3
0 VDC
4
+V
24 VDC
4 – 20 mA Signal
5
SIG
–V
6
0 VDC
7
+V
24 VDC
4 – 20 mA Signal
8
SIG
–V
9
0 VDC
10
+V
24 VDC
4 – 20 mA Signal
11
SIG
–V
12
0 VDC
TPPR
Three Wire Device
40
Touchpoint Pro
Technical Handbook