11 Configuring Modbus

Refer to the documentation supplied with the host computer for details of its communication and Modbus configuration.
Note: It is recommended that the host computer is configured to provide at least two retries in the event of a communication
loss with a minimum delay of 1 s between each poll, and a minimum timeout of 2 s.
Note: TPPR Modbus automatically uses two stop bits when parity is "None" and one stop bit when parity is "Odd" or "Even".
To configure the TPPR Modbus communication parameters:
1.
Login as an Engineer.
2.
From the System Status screen select the Tool Box icon then Global Settings.
3.
Select Modbus Settings> Edit to adjust the parameters.
4.
When complete, select Save and exit settings.
Parameter Name
Baud Rate
Parity
Primary Slave
Address
Secondary Slave
Address
11.1 Modbus Register Allocation for Function 02 – Read Input Status
This function reads the input channel status bits. Each status bit can have the value 1 = Active or 0 = Not active. For the
Channel Type only, 1 = Analogue or 0 = Digital. There are twelve status bits for each channel. The maximum number of
status bits read in one frame is 512.
Rate
LTEL
STEL
Channel
Alarm
Alarm
Alarm
01
10001
10002
10003
02
10017
10018
10019
64
11009
11010
11011
Rate
LTEL
STEL
Alarm
Alarm
Alarm
Channel
(Not
(Not
(Not
used)
used)
used)
5
11073
11074
11075
02
11089
11090
11091
128
13105
13106
13107
Part. No. 2400M2501_6
CONFIGURATION
Default Setting
9600
None
1
2

Table 17. Modbus Parameter Settings

Alarm 3
Alarm 2
Alarm 1
Inhibit
10004
10005
10006
10007
10020
10021
10022
10023
11012
11013
11014
11015

Table 18. Modbus Input Channels

Alarm 3
Alarm 2
(Not
(Not
Alarm 1
Inhibit
used)
used)
11076
11077
11078
11079
11092
11093
11094
11095
13108
13109
13110
13111

Table 19. Modbus Output Channels

Value Range
9600, 19200
Even, Odd, None
1 to 247
1 to 247
Channel
Not
Fault
No Data
Type
Used
10008
10009
10010
10011
10024
10025
10026
10027
11016
11017
11018
11019
Channel
Type
Force
Fault
No Data
(Not
State
used)
11080
11081
11082
11083
11096
11097
11098
11099
13112
13113
13114
13115
96
Comment
Should be set to correspond to the baud
rate of the host system.
Should be set to correspond to the parity
checking set on the host system.
Each node connected to the RS485
highway must have a different address
setting in daisy chain or multi-drop
configuration.
SIL Channel
Safe State
Warning
(Future Use)
(Future Use)
10012
10013
10014
10028
10029
10030
11020
11021
11022
SIL Channel
Safe State
Warning
(Future Use)
(Future Use)
11084
11085
11086
11100
11101
11102
13116
13117
13118
Not
Acknowledged
Used
10015
10016
10031
10032
11023
11024
Acknowledged
Free
11087
11088
11103
11104
13119
13120
Touchpoint Pro
Technical Handbook