9.3.3
Field Device Selection
Access Level: Administrator
Parameter
Value Range
Name
Field Device
Maximum 30
Type
Alphanumeric Characters
Sensor Variant
Maximum 30
Alphanumeric Characters
9.3.4
Sensor Settings
Access Level: Administrator
Parameter Name
Gas Name
Gas Unit
Bridge Current
9.3.5
Range Settings
Access Level: Administrator
Parameter Name
Signal Range Min
Signal Range Max
Gas Range Min
Gas Range Max
Part. No. 2400M2501_6
CONFIGURATION
Comment
If the sensor catalogue is used, a list of available field devices will be
displayed for selection.
If copy channel is being used, this value cannot be changed
If the sensor catalogue is used, a list of available gases and ranges
will be displayed for selection.
If copy channel is being used, this value cannot be changed
Default Setting
Value Range
Maximum 10 Alphanumeric
Characters
%FSD, %LEL, % Vol., ppm, ppb,
mA, mV, mg/m3, LEL.m or
maximum 5 Alphanumeric
Characters
200 mA
180 to 360 mA
Default Setting
Value Range
0
0 mV to 100 mV x = Measured signal value
Depends on
5 mV to 300 mV
sensor type
selected
0
0 to 99999
depending on
selected sensor
type.
Depends on
0.01 to 99999
sensor type
depending on
selected
selected sensor
type.
Comment
FSD – Full Scale Deflection
LEL – Lower Explosive Limit
LEL.m – LEL metres
Comment
X1 = Signal Range Min (Electrical input from Sensor)
X2 = Signal Range Max (Electrical input from Sensor)
Y1 = Gas Range Min
Y2 = Gas Range Max
Gas concentration (y) is calculated as follows:
y = (((Y2-Y1)/(X2-X1))*(x-X1))+Y1
Note: Signal Range Min and Max are over-written during
calibration, and are then no longer editable
76
Touchpoint Pro
Technical Handbook