TECHNICAL SPECIFICATIONS

21.4 Power Supplies and Fuses

21.4.1 Power Supply Units
Power Supply
Input Voltage Range
Input Frequency Range
Input AC current
Output Voltage
DC OK Relay contact ratings
(max.)
Protection
Dimension
Operating Temperature
De–rating (60°C to 70°C)
Storage Conditions
Operating Humidity
21.4.2 DIN Rail (Module Supply and Communication)
Description
Total Width
Type
21.4.3 Ring Coupling Module (RCM)
Description
Electrical Connection
Supply Voltage
Power Consumption
Power Dissipation
Ring Network Cable
Operating Temperature
Storage Temperature
Environmental Protection Class Equipment Class III, Installation Cat 2, Pollution Degree 2
Part. No. 2400M2501_6
120 W (5 A)
85 – 276 VAC; 88 – 187 VDC
50 – 60 Hz ± 6%
1.10 A at 120 VAC
0.62 A at 230 VAC
DC 24 V (Adjustable 24 – 28 VDC)
60 VDC @ 0.3 A / 30 VDC @ 1 A / 30 VAC @ 0.5 A resistive load
Short Circuit, Overload protected. Over-Volt, Over-Temp
40 x 124 x 117 mm
(W x H x D)
–25 °C to +60 °C (–13 °F to +140 °F)
3 W / °C
–40° to +85° C (–40° F to +185° F), 5 to 95 %RH (non–condensing)
5 to 95 %RH (non–condensing)
Standard DIN Rail – used for mounting Power Supplies, Backplanes and Modules
430 mm / 487 mm (Options)
TS–35/15
Module for signal connection of DIN Rail mounted I/O modules to Ring Network
2 x Ring Network TX / RX Driver Pairs (Each two-wire plus Drain)
18 – 32 VDC
Maximum 1 W
Maximum 1 W
Good quality RS485, shielded twisted pair plus Drain and Overall Screen
–40°C to +70°C
–40°C to +70°C
169
240 W (10 A)
2.22 A at 120 VAC
1.22 A at 230 VAC
60 x 124 x 117 mm
(W x H x D)
6 W / °C
480 W (20 A)
4.56 A at 120 VAC
2.48 A at 230 VAC
82 x 124 x 117 mm
(W x H x D)
12 W / °C