POTENTIAL OPERATING ISSUES
Error
Message
Code
68
The Network Initialisation failed;
the Ring Network is interrupted.
Please check the Ring Network
wiring as explained in the user
manual and retry the
initialisation once the
interruption is rectified.
69
Not used
70
Cannot clear Inhibit because the
channel has been inhibited
automatically
71
Cannot reset because the alarm,
fault or warning is still active
72
One or more events are still
active and cannot be reset
73
Replace operation cannot be
performed; module type of new
module is not compatible.
74
Not used
75
Not used
76
Not used
77
Not used
78
Not used
Part. No. 2400M2501_6
Possible Cause
Remedial Action
The system will not
See Chapter 19 Ring Communication Errors
allow you to initialise
1. Check the Active Events screen for details of
the network if a ring
the location of the connection break.
break is present
2. Check the cables and connections in the
area where the connection break fault is
indicated (also see Error 37).
3. Ensure that details of the Ring Network
break error have gone from the Active Events
screen (problem is resolved)
4. Return to the System Setup screen and retry
the Ring Initialisation operation.
A mV input channel
1. For a mV channel, calibrate the channel (see
has not yet been
Commissioning, Calibrating a mV input
calibrated or channel
channel).
configuration was
2. If this is not the cause, go to System
interrupted, or the
Configuration, then System Setup.
inhibit delay time is
3. Select the module with the inhibited channel,
active, or the
and select Normal State.
sensor/transmitter is
4. If this is not successful, go to Tool Box then
signalling inhibit
Event History to check if an Inhibit Delay Time
is active. The inhibit condition will clear after
the Delay Time has expired.
5. If there is no Delay Time active, then
investigate the conditions at the
sensor/transmitter.
The field device is still
Investigate the conditions at the field device.
signalling an active
alarm, fault or
warning
Cleared alarms, faults
Some events (for example Over Range
Warning) may give multiple alarms and these
or warnings have
been reset, but others
must all be investigated and cleared at the
are still active
respective field devices before attempting to
reset again.
Replacement module
1. Check and confirm that the replacement
is incorrect type or
module is of the correct type.
not recognised by the
2. Re-initialise the ring network and try again.
CCB
3. If the error persists, update the CCB
firmware.
4. If the problem persists, please contact your
local service representative.
153
Sys
Sys
Fail
Fault
Relay
Relay
Touchpoint Pro
Technical Handbook