Control Module And User Interface - Honeywell Touchpoint Pro Technical Handbook

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

TECHNICAL SPECIFICATIONS

21.5 Control Module and User Interface

21.5.1 Controller & Remote Unit DC Input Supply
Input Voltage
DC Input Voltage Range
21.5.2 Control Module and User Interface
Description
Supply Voltage
Power Consumption
Ring Communication Physical
layer
Ring Network Cable
Relay Outputs
Relay Contacts
Interfaces
Panel Dimension
Retention of Real Time Clock
Part. No. 2400M2501_6
DC 24 V (nominal)
18 – 32 VDC (Supplied from Self Enclosed Low Voltage source only)
Front panel User Interface Assembly
18 – 32 VDC (Supplied from Self Enclosed Low Voltage source only)
Maximum 13 W
Isolated RS485
2
Two x 1 mm
twisted pair cable
Two x System State Relays
Min. 12 VDC, 10 mA
Max. 5 A at 250 VAC / 30 VDC (non–inductive)
5.7 inch, 320 x 240 pixels (QVGA), Touch Screen LCD
LED and Button Panel with LEDs for Power, Alarm and Fault indication.
Buttons for Accept and Reset functions
Buzzer for audio indication of Alarm/Faults (Sound Level: 85 dB at 100 mm)
USB 2.0 Device Interface with standard Type B USB connector to interface with
PC/Laptop for configuration. Supports FAT32 USB memory device up to 32 Gb.
Industrial grade devices recommended.
Standard FAT32 SD Card Interface 4 Gb to 32 Gb
Supports 24 mm x 32 mm x 2.1 mm cards. Industrial grade cards recommended.
10/100 Mbps Ethernet Interface with standard RJ–45 connector
Two x RS–485 Modbus connections supporting maximum 115.2 kbps
483 mm x 222 mm
72 hours unpowered
173
Touchpoint Pro
Technical Handbook

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tppr

Table of Contents