TECHNICAL SPECIFICATIONS
21.6.5 Relay Output Module
Description
Electrical Connection
Supply Voltage (Vs)
Auxiliary Supply Voltage
Auxiliary Supply Current
Power Consumption
Power Dissipation
Relay Contacts (TB1–TB4)
Connector Coding
Part. No. 2400M2501_6
4–channel Relay Output Module incorporating 4 single pole change over (SPCO)
relays and 24 VDC Auxiliary Power Output
4 x SPCO Relay Terminals (TB1 to TB4)
4 x two-wire Auxiliary Output Terminals (TB5 to TB8)
18 – 32 VDC
Supply Voltage (Vs) – 0.7 V
Maximum 1.5 A
Maximum 1.5 W (excluding auxiliary power consumption)
Maximum 2.3 W
Maximum 5 A through one relay contact at 250 VAC / 30 VDC (non–inductive)
Maximum 8 A total through all four relay contacts at 250 VAC / 30 VDC (non–
inductive) Minimum 12 VDC, 10 mA
Relay output connectors (TB1–TB4) and auxiliary output connectors (TB5–TB8)
have coding keys to avoid incorrect wiring
The relay output connectors (TB1–TB4) are coloured black to identify them
for AC supply wiring