Tppr Specifications; Rack Mounted Equipment - Honeywell Touchpoint Pro Technical Handbook

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

TECHNICAL SPECIFICATIONS

21 TPPR Specifications

This section contains basic information about the various TPPR major equipment and assemblies, and the terms 'Local' and
Remote' refer to the unit's physical location in relation to the control room.
Note 1: Power Supply Fluctuations are not to exceed DC 18 – 32 V SELV Supply or ±10 % of nominal.
Note 2: All equipment in this manual is rated to +2000 m (6562 ft.) altitude maximum.
Note 3: All rack-mounted enclosures are Equipment Class 1 (grounded) and Installation Category 2.

21.1 Rack Mounted Equipment

This apparatus must be installed in a suitable enclosure which provides a Pollution Degree 2 environment in
Cet appareil doit être installé en zone sure dans un boitier conforme au niveau 2 de pollution environnementale.
This apparatus must be installed in a suitable enclosure which provides at least IP20 / Type 1 to mitigate the risk of
21.1.1 OEM 19 inch 5U Assembly (Local)
Front Panel Controller, which includes mounting brackets, UI, PCBs and SD Card.
Part Number
Material
Earth (Ground) Points
Dimensions (H x W x D)
Weight
Electrical Rating
Relay Contacts
Class
Altitude
Pollution Degree
Ambient Temperature
Humidity
Ingress Protection
*Note: to maintain the Type 1 and IP 2X ratings this panel must be fitted to an equivalent certified rack enclosure designed for
use with this front panel with no more than a 6 mm gap that provides a Pollution Degree 2 environment when fitted together in
accordance with the manufacturer's instructions. It is the end user's responsibility to ensure that the rack system meets all relevant
approvals, including ensuring adherence to temperature ratings when installed in the end unit/system.
Part. No. 2400M2501_6
ordinary (safe area) locations.
AVERTISSEMENT
TPPR-V-0602
Mild Steel
M8 (main grounding) other M6
483 x 222 x 110 mm
12 Kg with controller assembly; 6 Kg without
24 VDC nominal (18 – 32 VDC); 13 W max.
(W max is dependent on module and PSU configuration.)
250 VAC; 50/60Hz; 30 VDC; 5 A max.
Equipment Class 1 (grounded)
2000 m ASL max. in permanently-connected continuous operation.
2
–20 °C to +65 °C
10 to 90 %RH non-condensing
N/A (See below for special considerations*)
WARNING
WARNING
electrical shock.
164