Honeywell Touchpoint Pro Technical Handbook page 161

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

POTENTIAL OPERATING ISSUES
Error
Message
Code
79
The Input Module cannot be
commissioned: The maximum
number of 16 Input Modules has
already been commissioned on
the system.
80
The Output Module cannot be
commissioned: The maximum
number of 32 Output Modules
has already been commissioned
on the system.
81
Invalid test sequence
82
The user could not be added;
invalid user name. Please
choose a different user name
and try again.
83
Kill Session denied
Configuration Backup / Restore
in Progress
84
Kill Session denied CCB
Firmware update in Progress.
85
The controller needs a restart to
proceed further. Please power
cycle the controller and try
again.
86
System is running in test mode.
87
Not used
88
Operation failed; Save
Calibration Failed.
89
Operation failed; Channel Wiring
Fault.
90
Operation failed; Bead Fault.
Part. No. 2400M2501_6
Possible Cause
Remedial Action
TPPR has a
If more channels than 64 inputs and 128
maximum capacity of
outputs are required an additional TPPR
16 Input and 32
system is needed. Contact your local
Output Modules
representative to discuss your requirements
———//———
————————//————————
CCB receives wrong
Refer to Error 2
Test sequence for
Relay tests
The user name must
Please choose a user name that meets the
be 4 to 20 characters
requirements and try again
long
User has attempted
Retry after the configuration restore operation
to end a session for
is completed.
the PC configuration
Check with the user at the local controller that it
SW while a CCB
is acceptable to log in from remote PC.
configuration backup
or restore is in
progress
User has attempted
Retry after the firmware download operation is
to end a session for
completed.
the PC configuration
Check with the user at the local controller that it
SW while a CCB
is acceptable to log in from remote PC.
firmware update is in
progress
The system is being
Cycle the power supply off, wait 15 to 20
updated and needs a
seconds and then power on again
power cycle to
continue.
One of the three test
Wait until testing is complete. If necessary, exit
modes is active, and
Test Mode to carry out the required operation.
other operations are
restricted or not
permitted
TPPR was unable to
Please retry the operation.
save the sensor
calibration
TPPR cannot detect
Check all field wiring to the sensor and correct
that a sensor is
any problems
connected to the
channel or it has
detected incorrect
wiring
TPPR cannot read
Check all field wiring to the sensor. It is
the bead current from
possible that the sensor has failed, Refer to the
manufacturer's instructions
the connected mV
sensor
154
Sys
Sys
Fail
Fault
Relay
Relay
X
X
X