Table 4. Dc-Ups Primary Terminal Allocation; Table 5. Dc-Ups Secondary Terminal Allocation - Honeywell Touchpoint Pro Technical Handbook

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

3.4.3
DC Uninterruptible Power Supply (DC-UPS) Module
The DC-UPS Module can be used with the separate and optional TPPR Battery Enclosure to provide continuous and
uninterrupted power to the TPPR in the event of an external power failure.
The DC-UPS is adjustable for buffer time and buffer voltage, and carries red, yellow and green status LEDs and descriptions
that show your backup battery status (see tables below).
Note: The DC-UPS Module Buffer Voltage should be set at 26 VDC to ensure optimum battery charging, and the Buffer-time
Limiter should usually be set to ∞ (see circled area on the figure below).
The DC-UPS terminals are as follows:
Input +
Input –
Input –
Output +
Output –
Battery +
Battery –
The DC-UPS also has Normally Open (NO) relay terminals that can be used for external repeaters such as a lamp stack or
alarm buzzer, as shown in the table below:
DC-UPS Terminal
1 & 2
3 & 4
5 & 6
7 & 8
11 – 13
Part. No. 2400M2501_6
INTRODUCTION
Figure 29.
DC-UPS and Battery Configuration
DC-UPS Terminal
Purpose
+24 VDC input from UPS
–24 VDC input from UPS
–24 VDC input from UPS (spare)
+24 VDC output to 20 A (max) Load
–24 VDC output to 20 A (max) Load
+24 VDC Battery in/out
+24 VDC Battery in/out

Table 4. DC-UPS Primary Terminal Allocation

Purpose
Ready relay: Closed when all is Ok (green)
Buffering relay: Closed when batteries are supplying power (yellow or buzzer)
Replace Battery relay: Closed when batteries fail load test (red or buzzer)
Do not use as Inhibit belongs to the Controller only
Not normally used

Table 5. DC-UPS Secondary Terminal Allocation

24 VDC
20 A
12 VDC
12 VDC
Battery
Battery
Isolator
Switch
22
24 VDC
20 A max
Load
Touchpoint Pro
Technical Handbook

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tppr

Table of Contents