VR9105V, F AND VR9205V, F DIRECT IGNITION GAS CONTROL WITH INTEGRATED 1:1 REGULATOR
TWO IMPERFECT
THREADS
GAS CONTROL
PIPE
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO GAS CONTROL
Fig. 5. Use moderate amount of pipe compound.
Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before making wiring
connections. More than one disconnect may be
involved.
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or use the general instructions
provided below. When these instructions differ from the
appliance manufacturer, follow the appliance
manufacturer instructions.
All wiring must comply with applicable electrical codes
and ordinances.
1. Disconnect power supply before making wiring con-
nections to prevent electrical shock or equipment
damage.
2. Check the power supply rating on the gas control
and make sure it matches the available supply.
Install a transformer and other controls as required.
3. Connect the control circuit to the gas control
terminals.
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
M3075B
Fig. 6. Proper use of wrench on gas control.
4. Ensure combustion chamber is free of gas before
startup.
5. Adjust thermostat heat anticipator to the rating
stamped on valve operator.

Electrical Connection

VR9105V, F and VR9205V, F can be connected to any
standard direct ignition control with 110 Vac output by
using rectifier plug 45900441-039 or 24 Vac output by
using rectifier plug 45900441-015 or to 24 Vdc output by
using plug without rectifier 45900441-029. To secure the
plug to the valve use mounting screw applying 5.5 ± 1.5
LB-IN torque.
CAUTION
Equipment damage.
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve
coil terminals, even temporarily.
IMPORTANT
These gas controls are shipped with protective
seals over the inlet and outlet ports. Do not
remove the seals until ready to install adapters
or connect the piping.