Honeywell Touchpoint Pro Technical Handbook page 128

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

14.7.1 Event Status with a Rising Gas Reading
Rising Gas Reading
Below 100%
≥100% & <120%
≥120%
14.7.2 Event Status as the Gas Concentration Decreases
The indicated value remains at the programmed Over Range Warning value. A "greater than" symbol (">") is displayed to
indicate that the programmed level has been exceeded. The latched reading may be reset once the gas concentration has
decreased below the programmed level.
The Over Range Warning remains Latched.
Note: In the following example, Full Scale Exceeded will not reappear until the gas concentration falls to between 100% &
120% of the pre-set gas range and the latched Over Range Warning has been reset manually.
Falling Gas Concentration
≥100% & <120%
≥100% & <120%
Below 100%
Part. No. 2400M2501_6
NORMAL OPERATION
Event Status
(Full scale/Over
Range)
Full Scale Exceeded
Active
Over Range Warning
Active
Table 41. Rising Gas Reading
WARNING
A potentially explosive gas concentration may still exist at this point.
Event Status (Full
Scale/Over Range)
Over Range Warning
still Active (latched)
Full Scale Exceeded
Table 42. Falling Gas Reading
121
Event History
(Sequential Entries)
Full Scale Exceeded Active
Full Scale Exceeded Active
Full Scale Exceeded Cleared
Over Range Active
Event History
(Sequential Entries)
Full Scale Exceeded Active
Full Scale Exceeded Cleared
Over Range Active
Full Scale Exceeded Active
Full Scale Exceeded Cleared
Over Range Active
Over Range Cleared
Full Scale Exceeded Active
Full Scale Exceeded Active
Full Scale Exceeded Cleared
Over Range Active
Over Range Cleared
Full Scale Exceeded Active
Full Scale Exceeded cleared
Remarks
Full Scale Exceeded auto-
cleared (overwritten by Over
Range Warning)
Remarks
Full Scale Exceeded is hidden
while Over Range Warning is
active.
st
1
manual reset attempted by
user.
Over Range Warning reset
was successfully.
Full Scale Exceeded may
appear.
nd
The 2
manual reset can be
applied now and Full Scale
Exceeded should auto-clear.
Touchpoint Pro
Technical Handbook

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tppr

Table of Contents