POTENTIAL OPERATING ISSUES
Error
Message
Code
103
Not used
104
Operation failed; response result
failure
105
Operation failed; response
timeout
106
Operation failed; CRC error
107
Operation failed; session
expired
108
CCB-COB communication
failed.
109
Operation failed; CCB is not
responding.
110
Channel cannot be
commissioned; no free Channel
ID available.
111
Operation failed; invalid
command code received from
CCB.
112
Module cannot be
commissioned. You have
exceeded the maximum number
of 48 I/O modules. Use the
Remove Module or Replace
Module function in the System
Configuration.
113
Not used
114
Restore operation failed -
backup file could not be found
115
Operation cannot be performed -
please insert SD Card!
Part. No. 2400M2501_6
Possible Cause
Remedial Action
Internal
1. Please retry the operation.
communication error
2. If still unsuccessful, on the front panel, press
the Accept and Reset buttons together for 10 s,
which will restart the COB.
3. If the error has not cleared, if possible cycle
the power to the system.
4. If the problem persists, please contact your
local service representative.
———//———
————————//————————
———//———
————————//————————
A user login will time
The system will automatically request a new
out after 20 minutes
login
of inactivity
Refer to Error 2
Refer to Error 2
———//———
————————//————————
Each TPPR system is
Contact your local representative if you want to
limited to 64 input and
discuss any requirements above this limit.
128 output channels
maximum
Refer to Error 2
Refer to Error 2
Each TPPR system is
Contact your local representative if you want to
limited to 16 Input
discuss any requirements above this limit.
plus 32 Output
Modules maximum
An error occurred
1. Check that you have specified the correct
during configuration
memory device, SD or USB.
restore
2. Check that the correct file is being used for
the restore operation, and is saved as \Hard
Disk\TPPR Configuration\
TPPR_Config_<SystemID>_<nnn>.bin, where
nnn is 001 to 999
3. Retry the operation.
4. On the front panel, press the Accept and
Reset buttons together for 10 s, which will
restart the COB.
5. Retry the operation.
1. Check that the SD Card has enough free
memory available for the operation.
2. Check that it is correctly inserted in the
socket.
3. Retry the operation.
156
Sys
Sys
Fail
Fault
Relay
Relay
X