9.5 Relay Output Module Parameters

Relay Output Module (ROM) channels may be configured as blank channels, or by copying an existing configured channel.
If configured by copying another channel, it is possible to edit individual settings.
Note that if there is a system failure all ROM module relays will de-energise, regardless of their configured states.
9.5.1
Commission Channel
Access Level: Administrator
Parameter Name
Channel ID
Channel Tag
Channel Custom ID
Note: Channel Tag and Channel Custom ID only require Engineer level access for editing
9.5.2
Relay Output Settings
Access Level: Engineer
Parameter
Default Setting
Name
Normal State
De-energised
Latch Function
Non-Latching
Delay Time
00m:00s
Hold Time
00m:00s
Auxiliary Output
Disabled
Enable
Alarm Update
Enabled
Enable
Action on New
Steady
Event
Note: Action on New Event only applies if Alarm Update function is enabled.
Part. No. 2400M2501_6
CONFIGURATION
Default Setting
Next available
'Channel <Channel ID>'
'Channel <Channel ID>'
Value Range
De-energised /
Energised
Non-Latching /
Latching
00m:00s to 05m:00s
00m:00s to 60m:00s
Enabled / Disabled
Enabled / Disabled
Steady / Pulsed
Value Range
Comment
1 to 128
Can only be assigned during first time
configuration. Otherwise de-commission the
channel and re-assign another channel number
Maximum 30
30 character location tag name. This is the main
Alphanumeric
channel description used throughout the interface
Characters
Maximum 20
20 character custom ID. This is displayed on the
'Channel Details' screen and in the Configuration
Alphanumeric
Characters
Report
Comment
The NC contact is closed
The alarm conditions are usually already configured
as latching; therefore the output channel is
configured non-latching as the default setting.
The output module will activate the output channel
after the 'Delay Time' interval has expired. This
only applies for the transition 'normal to active'.
The output module will set the output channel into
normal condition after the 'Hold Time' interval has
expired. This only applies for the transition 'active
to normal' and only if the output is configured as
non-latching.
If enabled the system will report any auxiliary
output overload as a fault. The overload condition
applies to the module, so it will be reported on all
enabled channels.
If enabled, only unacknowledged alarm conditions
will be considered during C&E evaluation for this
output channel.
An alarm acknowledgement will reset a relay output
that is configured for alarm update function.
However if the alarm update is NOT enabled the
relay contact will only be reset if the alarm is reset.
Default is set to hold the relay on, but could be set
to pulse the output, e.g. for a beacon or sounder.
84
Touchpoint Pro
Technical Handbook