Honeywell Touchpoint Pro Technical Handbook page 172

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

TECHNICAL SPECIFICATIONS
21.1.2 Rack Unit Model 19 inch 5U Assembly (Local or Remote)
Supplied with a PSU and Modules; Local with a Controller, PCBs and SD Card.
Part Number
Material
Earth (Ground) Points
Dimensions (H x W x D)
Weight
Electrical Rating
Class
Altitude
Pollution Degree
Ambient Temperature
Humidity
Ingress Protection
*Note: to maintain the Type 1 and IP 2X ratings this panel must be fitted to an equivalent certified rack enclosure designed for
use with this front panel with no more than a 6 mm gap that provides a Pollution Degree 2 environment when fitted together in
accordance with the manufacturer's instructions. It is the end user's responsibility to ensure that the rack system meets all relevant
approvals, including ensuring adherence to temperature ratings when installed in the end unit/system.
21.1.3 OEM Unit 5U Assembly Only
Front Panel Controller, which includes UI, PCBs and SD Card but no mounting brackets.
Part Number
Material
Earth (Ground) Points
Dimensions (H x W x D)
Weight
Electrical Rating
Relay Contacts
Class
Altitude
Pollution Degree
Ambient Temperature
Humidity
Ingress Protection
*Note: to maintain the Type 1 and IP 2X ratings this panel must be fitted to an equivalent certified rack enclosure designed for
use with this front panel with no more than a 6 mm gap that provides a Pollution Degree 2 environment when fitted together in
accordance with the manufacturer's instructions. It is the end user's responsibility to ensure that the rack system meets all relevant
approvals, including ensuring adherence to temperature ratings when installed in the end unit/system.
Part. No. 2400M2501_6
TPPR-S-XXXX
Mild Steel
M8 (main grounding) other M6
483 x 222 x 110 mm
12 Kg with interface, 6 Kg without
100 – 240 VAC (±10 % of nominal supplied voltage), 50/60 Hz, 5 A max, Power Factor > 0.9
or 24 VDC nominal (18 – 32 VDC) 20 A max.
(W max is dependent on subsequent module and PSU configuration.)
Equipment Class 1 (grounded)
2000 m ASL max. in permanently-connected continuous operation.
2
–40 °C to +70 °C max.
–20 °C to +65 °C (Local with Controller)
–25 °C to +65°C (70 °C de-rated) (Remote with PSU but no Controller)
10 to 90 %RH non-condensing
Type1 / IP2X*
TPPR-V-0852
Mild Steel w. Membrane panel
M8 (main grounding) other M6
225 x 360 x 70 mm
4 Kg
24 VDC nominal (18 – 32 VDC); 13 W max.
(W max is dependent on subsequent module and PSU configuration.)
250 VAC; 50/60Hz; 30 VDC; 5 A max.
Equipment Class 1 (grounded)
2000 m ASL max. in permanently-connected continuous operation.
2
–20 °C to +65 °C
10 to 90 %RH non-condensing
N/A (See below for special considerations*)