Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
Settings
2.2.13
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
1201
FCT 50/51
1202
50-2 PICKUP
1203
50-2 DELAY
1204
50-1 PICKUP
1205
50-1 DELAY
1207
51 PICKUP
1208
51 TIME DIAL
1208
51 TIME DIAL
1209
51 TIME DIAL
1210
51 Drop-out
1211
51 IEC CURVE
1212
51 ANSI CURVE
1213A
MANUAL CLOSE
1214A
50-2 active
1215A
50 T DROP-OUT
1216A
50-3 active
1217
50-3 PICKUP
1218
50-3 DELAY
96
C
Setting Options
ON
OFF
1A
0.10 .. 30.00 A; ∞
5A
0.50 .. 150.00 A; ∞
0.00 .. 7200.00 sec; ∞
1A
0.10 .. 30.00 A; ∞
5A
0.50 .. 150.00 A; ∞
0.00 .. 7200.00 sec; ∞
1A
0.02 .. 4.00 A
5A
0.10 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.01 .. 20.00 sec; ∞
0.50 .. 15.00 ; ∞
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50-3 instant.
50-2 instant.
50 -1 instant.
51 instant.
51-1 instant.
51-2 instant.
51-3 instant.
51-4 instant.
Inactive
Always
with 79 active
0.00 .. 60.00 sec
Always
with 79 active
1A
1.00 .. 30.00 A; ∞
5A
5.00 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
Default Setting
Comments
ON
50, 51 Phase Time Overcur-
rent
4.00 A
50-2 Pickup
20.00 A
0.00 sec
50-2 Time Delay
1.00 A
50-1 Pickup
5.00 A
0.50 sec
50-1 Time Delay
1.00 A
51 Pickup
5.00 A
0.50 sec
51 Time Dial
0.50 sec
51 Time Dial
5.00
51 Time Dial
Disk Emulation
Drop-out characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
50-2 instant.
Manual Close Mode
Always
50-2 active
0.00 sec
50 Drop-Out Time Delay
Always
50-3 active
∞ A
50-3 Pickup
∞ A
0.00 sec
50-3 Time Delay
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017