Functions
2.5 Single-Phase Overcurrent Protection
Addr.
Parameter
1631
I/IEp Rf T/TEp
1634
67N-3 PICKUP
1635
67N-3 DELAY
1636
67N-3 Direction
1637A
67N-3 MEASUREM.
1638
67N-3 w. Inrush
1639A
67N-3 active
1640
67N-TOC-1 Dir.
1641
67N-TOC-2 Dir.
1642
67N-TOC-3 Dir.
1643
67N-TOC-4 Dir.
1644
67N-TOC-1 PU
1645
67N-TOC-1 TD
1646A
67N-TOC-1 MEAS.
1647
67N-TOC-1 Drop.
1648
67N-TOC-1 IEC
1649
67N-TOC-1 T ad.
1650
67N-TOC-2 PU
1651
67N-TOC-2 TD
1652A
67N-TOC-2 MEAS.
1653
67N-TOC-2 Drop.
182
C
Setting Options
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
0.50 .. 30.00 A; ∞
0.00 .. 60.00 sec; ∞
Forward
Reverse
Non-Directional
Fundamental
True RMS
NO
YES
always
with 79 active
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Fundamental
True RMS
Instantaneous
Disk Emulation
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
0.00 .. 30.00 sec
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Fundamental
True RMS
Instantaneous
Disk Emulation
Default Setting
Comments
67N TOC
∞ A
67N-3 Pickup
0.00 sec
67N-3 Time Delay
Forward
67N-3 Direction
Fundamental
67N-3 measurement of
NO
67N-3 with Inrush Restraint
always
67N-3 active
Forward
67N-TOC-1 Direction
Forward
67N-TOC-2 Direction
Forward
67N-TOC-3 Direction
Forward
67N-TOC-4 Direction
1.00 A
67N-TOC-1 Pickup
5.00 A
0.50 sec
67N-TOC-1 Time Dial
Fundamental
67N-TOC-1 measurement
of
Disk Emulation
Drop-Out Characteristic
Normal Inverse
67N-TOC-1 IEC Curve
0.00 sec
Constant time adder 67N-
TOC-1
1.00 A
67N-TOC-2 Pickup
5.00 A
0.50 sec
67N-TOC-2 Time Dial
Fundamental
67N-TOC-2 measurement
of
Disk Emulation
Drop-Out Characteristic