Communication Module Configuration - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Mounting and Commissioning
3.3 Commissioning
Test in Command Direction
The information transmitted in command direction must be indicated by the central station. Check whether
the reaction is correct.

Communication Module Configuration

3.3.3
Required Settings in DIGSI 4
The following applies in general:
In the case of a first-time installation or replacement of a communication module, the ordering number
(MLFB) does not need to be changed. The ordering number can be retained. Thus, all previously created
parameter sets remain valid for the device.
Changes in the DIGSI Manager
In order that the protection device can access the new communication module, a change has to be made in
the parameter set within the DIGSI Manager.
In DIGSI 4 Manager, select the SIPROTEC device in your project and select the menu item Edit - Object prop-
erties... to open the Properties - SIPROTEC 4 Device dialog box (see following figure ). In the Communica-
tion modules tab, select the type of communication module or the protocol for 11. Port F using the L: ...
button.
[7sc80-protocol-110111, 1, en_US]
Figure 3-26
Mapping File
For DNP3.0, a matching bus mapping has to be selected.
For the selection of the mapping file, you can open the SIPROTEC device in DIGSI and choose the function
Interfaces in Parameter (see following figure).
480
DIGSI 4: Protocol selection (example)
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017