Non-directional Overcurrent Protection, ground
The dynamic pickup thresholds for the ground currents of the overcurrent protection are set at the following
addresses:
50Nc-1 PICKUP
50Nc-2 PICKUP
50Nc-3 PICKUP
51Nc PICKUP
51Nc-1 PICKUP
The tripping times for the ground currents of the overcurrent protection are set at the following addresses:
50Nc-1 DELAY
50Nc-2 DELAY
50Nc-3 DELAY
51Nc T-DIAL
51Nc T-DIAL
51Nc T-DIAL
51Nc-1 T-DIAL
The characteristics for the ground currents of the overcurrent protection and their possible settings are
entered at addresses:
1911 51c IEC Curve
1912 51c ANSI Curve
1913 51Nc Recloser
1917 51Nc-1 IEC Cu.
1919 51Nc-1 ANSI Cu.
1920 51Nc-1 Rec. Cu.
At address 1910 51c Drop-out or 1916 51Nc-1 Drop-out, you can set the dropout behavior Disk
Emulation or Instantaneous for the ground currents of the overcurrent protection.
Directional Overcurrent Protection, Phases
The dynamic pickup thresholds for the phase currents of the overcurrent protection are set at the following
addresses:
50c-1 PICKUP
50c-2 PICKUP
67c-3 PICKUP
51c PICKUP
67c-TOC-1 PU
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Address 1903
Address 1901
Address 1908
Address 1905
Address 1914
Address 1904
Address 1902
Address 1909
Address 1906 for IEC and user-defined characteristics
Address 1906 for recloser characteristics. The parameter must cover an extended
setting range by the bandwidth of the recloser characteristic
Address 1907 for ANSI characteristics
Address 1915 for setting value all curves
Normal Inverse, Very Inverse, Extremely Inv., Long
Inverse
Very Inverse, Inverse, Short Inverse, Long Inverse,
Moderately Inv., Extremely Inv., Definite Inv.
Curve A (101), Curve B (117), Curve C (133), Curve D
(116), Curve E (132), Curve K (162), Curve N (104), Curve
R (105), Curve W (138), Curve 2 (135), Curve 3 (140),
Curve 8 (113), Curve 8* (111), Curve 9 (131), Curve 11
(141)
Normal Inverse, Very Inverse, Extremely Inv., Long
Inverse
Very Inverse, Inverse, Short Inverse, Long Inverse,
Moderately Inv., Extremely Inv., Definite Inv.
Curve A (101), Curve B (117), Curve C (133), Curve D
(116), Curve E (132), Curve K (162), Curve N (104), Curve
R (105), Curve W (138), Curve 2 (135), Curve 3 (140),
Curve 8 (113), Curve 8* (111), Curve 9 (131), Curve 11
(141)
Address 2003
Address 2001
Address 2008
Address 2005
Address 2014
Functions
2.4 Dynamic Cold Load Pickup