Siemens 7SC80 Manual page 693

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr. Parameter
9511
Sec. CLP PU
9512
Sec. CLP PU T
9513
Sec. CLP DO
9514
Sec. CLP DO T
9521
Open Sec. Cnt.
9522
Min. Iph
9523
Min. Ignd
9524
Min. Iph CLP
9525
Min. Ignd CLP
9526
T. to con. Trip
9527
Time to open
9528
Time to reset
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
Sectionalizer
1A
0.04 .. 5.00 A
5A
0.20 .. 25.00 A
Sectionalizer
0.00 .. 360.00 sec
Sectionalizer
1A
0.04 .. 5.00 A
5A
0.20 .. 25.00 A
Sectionalizer
0.00 .. 360.00 sec
Sectionalizer
1 .. 20
Sectionalizer
1A
0.04 .. 30.00 A; ∞
5A
0.20 .. 150.00 A; ∞ 10.00 A
Sectionalizer
1A
0.04 .. 30.00 A; ∞
5A
0.20 .. 150.00 A; ∞ 2.50 A
Sectionalizer
1A
0.04 .. 30.00 A; ∞
5A
0.20 .. 150.00 A; ∞ 20.00 A
Sectionalizer
1A
0.04 .. 30.00 A; ∞
5A
0.20 .. 150.00 A; ∞ 5.00 A
Sectionalizer
0.01 .. 30.00 sec
Sectionalizer
0.00 .. 360.00 sec
Sectionalizer
0.00 .. 360.00 sec
Functions, Settings, Information
Default Setting
Comments
0.10 A
Sec. Cold Load Pickup
0.50 A
0.10 sec
Sec. Cold Load Pickup
Time Delay
0.20 A
Sec. Cold Load Drop-out
1.00 A
10.00 sec
Sec. Cold Load Drop-out
Time Delay
2
Open Sec. Counter
2.00 A
Minimum Phase Current
0.50 A
Minimum Neutral Current
4.00 A
Minimum Phase During
Cold Load
1.00 A
Minimum Neutral During
Cold Load
0.15 sec
Time to confirm trip
5.00 sec
Time to open command
10.00 sec
Time to reset after last
increase
F.2 Settings
693

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents