[lo_7sc80-sync-anschl, 1, en_US]
Figure 2-117
Voltage Difference
The parameters 6150 dV SYNCHK V2>V1 and 6151 dV SYNCHK V2<V1 can be set to adjust the permissible
voltage differences asymmetrically. The availability of two parameters enables an asymmetrical release to be
set.
Frequency Difference
The parameters 6152 df SYNCHK f2>f1 and 6153 df SYNCHK f2<f1 determine the permissible
frequency differences. The availability of two parameters enables an asymmetrical release to be set.
Operating Range
The parameters 6154 dα SYNCHK α2>α1 and 6155 dα SYNCHK α2<α1 delimit the operating range for
switching under synchronous system conditions. The availability of two parameters enables an asymmetrical
release range to be set.

Settings

2.20.7
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
6101
Synchronizing
6102
SyncCB
6103
Vmin
6104
Vmax
6105
V<
6106
V>
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Voltage Connection Phase-to-Phase Voltage, Example
Setting Options
ON
OFF
(Setting options depend on
the configuration)
20 .. 125 V
20 .. 140 V
1 .. 60 V
20 .. 140 V
Default Setting
Comments
OFF
Synchronizing Function
none
Synchronizable circuit breaker
90 V
Minimum voltage limit: Vmin
110 V
Maximum voltage limit: Vmax
5 V
Threshold V1, V2 without voltage
80 V
Threshold V1, V2 with voltage
Functions