Mounting and Commissioning
3.3 Commissioning
NOTE
i
i
If the mapping file assignment for a SIPROTEC device has been changed, this is usually connected with a
change of the allocations of the SIPROTEC objects to the system interface.
After having selected a new mapping file, please check the allocations to "Target system interface" or
"Source system interface" in the DIGSI allocation matrix.
Edit Field "Module-specific settings"
In the edit field Module-specific settings, only change the numbers in the lines not starting with // and
observe the semicolon at the end of the lines.
Further changes in the edit field might lead to an error message when closing the dialog box Interface
parameters. Please select the bus mapping corresponding to your requirements. The documentation of the
individual bus mappings is available on the Internet (www.siprotec.com in the download area).
Select the bus mapping corresponding to your requirements. The documentation of the individual bus
mappings is available on the Internet (www.siprotec.com in the download area).
After having selected the bus mapping, the area of the mapping file in which you can make device-specific
settings appears in the window (see the following figure). The type of this setting depends on the protocol
used and is described in the protocol documentation. Please only perform the described changes in the
settings window and confirm your entries with OK.
Then, transfer the data to the protection device.
[sc_dnp3-specific-setting, 2, en_US]
Figure 3-29
482
Module-specific Settings
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017